Throughout the 2025-2026 school year, I selected, tested, and implemented a new anemometer for the Turbine Monitoring System of the Streamlining Wind Turbines Collaboratory Project.

  • Electrical Design
  • Instrumentation
  • Measurement
  • EMF Shielding

Project Overview:

Skills Demonstrated
Electrical Design, Instrumentation, Measurement, EMF Shielding
Clients
WindAid Institute (Peru), Messiah University Collaboratory for Strategic Partnerships and Applied Research

Problem Statement

"In previous work cycles, the TMS used an ET-40AC anemometer, an AC-signal anemometer that would output a sinusoidal wave at a frequency that could be converted to wind speed. This anemometer suffered from high-frequency signal interference and significant difficulty with measuring the analog AC signal, and then converting it into a frequency. This resulted in low accuracy and high measurement uncertainty at low wind speeds."

Here shown is the anemometer circuit being checked with an oscilloscope (left). Each time the reed switch inside the ET-3250 opens and closes, the circuit produces one pulse, so the frequency of this square wave gives the wind speed (right). Below is our Turbine Monitoring System design record.

My primary contribution to this project was selecting, implementing, and testing the ET-3250 anemometer that replaced the ET-40AC. Rather than a sine wave, the ET-3250 opens and closes a reed switch as its cups spin, producing a square wave that is simpler and cheaper to measure and can be read alongside the system's other measurements.

Reading that square wave reliably meant hardening the circuit against electromagnetic noise. A pull-up resistor turns each opening and closing of the switch into a 0 to 3.3 V signal, the shielding on the anemometer cable is grounded, and an RC low-pass filter removes interference before a Schmitt trigger restores the square edges that the filter rounds off. In the final work cycle, I revisited the code and reworked the circuit so its capacitor could discharge correctly, which greatly shortened the falling edge of each pulse and gave the Schmitt trigger a much cleaner input.

To validate the final design, the anemometer recorded data for 7 days on the roof of Jordan and Kline Hall of Science. The results appeared free of noise for the entire period and matched the conditions we observed, and the ET-3250 covers wind speeds from 2 to over 40 m/s within ±0.45 m/s, meeting the system's requirement of ±0.5 m/s.